タイトルWind turbine generator interaction with diesel generators on an isolated power system
著者(英)Wilreker, V. F.; Scott, G. W.; Shaltens, R. K.
著者所属(英)Westinghouse Electric Corp.; NASA Lewis Research Center
発行日1983-07-01
言語eng
内容記述The results of a dynamic interaction investigation to characterize any disturbances caused by interfacing the Mod 0A wind turbine (150 kW configuration) with the Block Island utility diesel generator grid are reported. The tests were run when only two diesel generators were on line, and attention was given to power, frequency, and voltage time profiles. The interconnected system was examined in the start-up and synchronization phase, normal shutdown and cut-out of the wind turbine, during fixed pitch generation, and during variable pitch operation. Governors were installed on the diesel generators to accommodate the presence of wind-derived electricity. The blade pitch control was set to maintain power at 150 kW or below. Power and voltage transients were insignificant during start-up and shutdown, and frequency aberrations were within the range caused by load fluctuations. It is concluded that wind turbine generation can be successfully implemented by an isolated utility, even with a significant penetration to the total grid output.
NASA分類ENERGY PRODUCTION AND CONVERSION