タイトル | Gas distribution equipment in hydrogen service - Phase II |
著者(英) | Huang, H. D.; Jasionowski, W. J. |
著者所属(英) | Institute of Gas Technology |
発行日 | 1980-01-01 |
言語 | eng |
内容記述 | The hydrogen permeability of three different types of commercially available natural gas polyethylene pipes was determined. Ring tensile tests were conducted on permeability-exposed and as-received samples. Hydrogen-methane leakage experiments were also performed. The results show no selective leakage of hydrogen via Poiseuille, turbulent, or orifice flow (through leaks) on the distribution of blends of hydrogen and methane. The data collected show that the polyethylene pipe is 4 to 6 times more permeable to hydrogen than to methane. |
NASA分類 | ENERGY PRODUCTION AND CONVERSION |
レポートNO | 80A48506 |
権利 | Copyright |